Trane furnace error codes
This page explains the three-character display on the integrated furnace control of Trane S8X1 single-stage gas furnaces, using the August 2024 installation manual S8XB-SVX001-1D-EN. The supported models are S8X1A040M3PSCA, S8X1B040M2PSCA, S8X1B060M4PSCB, S8X1B080M4PSCB, S8X1C080M5PSCA, S8X1C100M5PSCB and S8X1D120M5PSCA. The PSC in these numbers is part of the model designation. It does not mean the blower is a PSC motor; this furnace uses a nine-tap blower. A code describes what the control detected, not a confirmed failed part.
Jump to the code table · All furnace codes
Before you touch anything: the six signs that mean stop troubleshooting and call a pro →
How to read the S8X1 control display
Read every character, including decimal points. These are display codes, not LED flash counts. During operation the display alternates every two seconds between the current mode and the requested blower tap (tP1 to tP9), and any error joins that rotation. Modes are IdL (idle), Ht (gas-heat demand), CP1 and CP2 (cooling or heat-pump demand), COf (continuous fan) and dFt (defrost with gas heat). Ht reflects the thermostat signal only and does not prove the burner is heating.
What this chart covers and excludes
The fault table lists all 15 codes that apply to the S8X1. E3.3 and E3.4 are second-stage codes and are excluded, as are E11's second-stage conditions. The manual's index shows E07 where the chart and detailed page show E7.1, and it reverses the E2.3 wording; this site follows the chart. tP blower-tap displays are status readouts, not heat faults. S8X1A026M2PSCA, S8X2, S9 and other control revisions are not covered.
- Trane S8X1 single-stage furnace control display (2024 IOM): S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA
Trane S8X1 fault codes (S8XB-SVX001-1D-EN)
| Code or flash pattern | Meaning | Model family | Details |
|---|---|---|---|
| E01Three-character display: E01 | Internal control failure E01 means the integrated furnace control (IFC) has detected an internal failure or an IRQ loss. The fault lies in the control board's own operation. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E2.1Three-character display: E2.1, alternating with status | Flame never established E2.1 means the furnace made three ignition attempts in one heat call and never sensed flame. The control then enters a one-hour lockout. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E2.2Three-character display: E2.2, alternating with status | Flame lost after lighting E2.2 means flame was established and then lost, and this repeated until ten recycles accumulated in one heat call. The control then enters a one-hour lockout. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E2.3Three-character display: E2.3, alternating with status | Gas valve not powered E2.3 means the control did not detect 24 VAC at the first-stage gas valve (MVL) when it was required, ten times in one heat call. The manual index states this backwards; the main chart and detailed page agree. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E3.1Three-character display: E3.1, alternating with status | Pressure switch closed E3.1 means the first-stage pressure switch is closed when the control expects it to be open. The manual notes that the switch itself is usually not the root cause. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E3.2Three-character display: E3.2, alternating with status | Pressure switch open E3.2 means the first-stage pressure switch is open when the control expects it to be closed, so the required draft has not been proven. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E04Three-character display: E04, alternating with status | Safety limit circuit open E04 means one of three safety switches is open: the main thermal limit, a flame rollout switch or the reverse-airflow switch. The code does not say which one tripped. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E05Three-character display: E05, alternating with status | Unexpected flame E05 means the control sensed flame at a time when no flame should be present. It is a safety fault, not a normal operating state. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E6.1Three-character display: E6.1, alternating with status | Reversed polarity E6.1 means the control detected reversed line-voltage polarity at the furnace power supply. It is an electrical supply fault, not a burner fault. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E6.2Three-character display: E6.2, alternating with status | Bad grounding E6.2 means the control has detected a poor ground connection. It points to the furnace's ground path, which needs electrical testing. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E6.3Three-character display: E6.3, alternating with status | Igniter circuit fault E6.3 means the igniter relay has failed or the igniter is open. The detailed diagnostic page also covers a relay stuck closed and an igniter circuit that is open or shorted. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E7.1Three-character display: E7.1, alternating with status | Gas valve powered when off E7.1 means 24 V is present at the first-stage gas valve circuit when it should be off. The manual index lists this as E07; that is a document inconsistency, not a confirmed alternate code. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E08Three-character display: E08, alternating with status | Low flame current E08 means flame current is low, below the 0.5 microamp DC threshold in the detailed diagnostics. The furnace is still allowed to operate; this is not a lockout. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E11Three-character display: E11, alternating with status | Gas valve relay fault On the S8X1, E11 means the first-stage gas valve was not energized when it should have been, or the first-stage valve relay is stuck closed. Second-stage conditions in the chart do not apply. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| E12Three-character display: E12, alternating with status | Control fuse open E12 means the 5 A fuse on the control board is open or missing. An open fuse suggests something in the low-voltage circuit drew too much current. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| IdLThree-character display: IdL | Idle IdL means idle: there is no cooling, heating or fan demand from the thermostat. The status reflects thermostat inputs, so it is normal when nothing is being called. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| HtThree-character display: Ht, alternating with blower tap every 2 seconds | Gas heat demand Ht means the control sees a gas-heat demand from the thermostat. It reflects the 24 VAC input only and does not confirm the burner lit or that heat is reaching the rooms. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| CP1Three-character display: CP1, alternating with blower tap | First-stage compressor CP1 means the thermostat is calling for first-stage cooling or heat-pump operation. It is a normal demand display, not a furnace fault. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| CP2Three-character display: CP2, alternating with blower tap | Second-stage compressor CP2 means the thermostat is calling for second-stage cooling or heat-pump operation. On the S8X1 this is a normal demand display, not a furnace fault. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| COfThree-character display: COf, alternating with blower tap | Continuous fan COf means the thermostat is calling for continuous fan. The blower runs without a heating or cooling call, so register air stays near room temperature. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |
| dFtThree-character display: dFt, alternating with blower tap | Defrost gas heat dFt means the outdoor heat pump has a defrost demand and the furnace is in gas-heat mode during that period. It is a normal demand state, not a fault. | S8X1A040M3PSCA · S8X1B040M2PSCA · S8X1B060M4PSCB · S8X1B080M4PSCB · S8X1C080M5PSCA · S8X1C100M5PSCB · S8X1D120M5PSCA | View details |