This page covers York TM9E single-stage ECM gas furnaces as documented in installation manual 6019630-UIM-F-0423. The control uses one LED that can show red, amber or green, and the color matters: four red flashes and four amber flashes mean different things. Confirm the full model number and the label on the installed furnace before relying on this chart, because other York and Johnson Controls furnaces and replacement boards can use different tables. A code describes what the control detected, not which part failed.

Jump to the code table · All furnace codes

Before you touch anything: the six signs that mean stop troubleshooting and call a pro →

How to read the tri-color LED

Fault codes are groups of flashes about a third of a second on and a third off, with a 2-second gap between groups. Note the color as well as the count. A slow flash of 2 seconds on and 2 seconds off is normal: green means no thermostat call, amber means a heat call is present. Slow amber does not prove the burner is lit, and it is not a one-flash fault. No LED, or an LED lit steadily in any color, points to a power or control problem. Read the LED through the existing viewing port.

What this chart covers

The chart has 16 live rows: eleven red fault codes (1 to 11), one amber warning of four flashes, two normal slow-flash states, and the no-LED and steady-on control states. Two green acknowledgements (2 and 3 flashes) appear only in the technician's LAST ERROR memory mode and are left out. Two amber flashes, a normal heating state for modulating furnaces only, does not apply to the single-stage TM9E. Models covered are the ten MP12 models from TM9E026A08MP12 to TM9E120D20MP12 listed in the TM9E technical guide.

TM9E LED code chart (manual 6019630-UIM-F-0423)

York furnace codes and supported model families
Code or flash pattern Meaning Model family Details
Red LED: 1 flash, then 2-second pause Flame Without Heat Call

The control sensed flame when there was no call for heat. In response it runs the combustion-air inducer and the supply-air blower.

TM9E View details
Red LED: 2 flashes, then 2-second pause Pressure Switch Closed

At the start of a heat cycle the pressure switch was already closed when the control expected it open. The control blocks the ignition sequence while this condition exists.

TM9E View details
Red LED: 3 flashes, then 2-second pause Pressure Switch Open

The control expected the pressure switch to be closed and found it open. York lists several checks for this, so the code alone does not prove a failed switch.

TM9E View details
Red LED: 4 flashes, then 2-second pause Main Limit Open

The main limit switch is open, and the supply blower and inducer keep running while it stays open. Five openings in one heat demand cause a 1-hour soft lockout; if it stays open past 5 minutes, the code changes to 11 red.

TM9E View details
Red LED: 5 flashes, then 2-second pause Rollout Switch Open

The manual-reset rollout safety switch has opened. The control goes into a hard lockout that York permits clearing only after the problem is corrected.

TM9E View details
Red LED: 6 flashes, then 2-second pause Pressure Switch Lockout

The pressure switch opened four times during one heat call. The control then locks out for one hour before an automatic retry.

TM9E View details
Red LED: 7 flashes, then 2-second pause Ignition Failure

The furnace made three ignition trials without establishing flame. The control then locks out for one hour and retries automatically.

TM9E View details
Red LED: 8 flashes, then 2-second pause Repeated Flame Loss

Flame was lost five times during heating, which corresponds to four recycles. The control locks out for one hour, then retries automatically.

TM9E View details
Red LED: 9 flashes, then 2-second pause Polarity or Ground Fault

The control has detected reversed line-voltage polarity, a grounding problem, or reversed low-voltage transformer wires. Heating and cooling are both affected, and ignition is blocked until it is corrected.

TM9E View details
Red LED: 10 flashes, then 2-second pause Gas Valve On Without Call

The control detects the gas valve energized when there is no call for heat. The inducer and main blower run, and no ignition sequence starts while it persists.

TM9E View details
Red LED: 11 flashes, then 2-second pause Limit Open Too Long

The main limit has stayed open for more than 5 minutes, putting the control in a hard lockout. York says the lockout should be cleared only after the problem is corrected.

TM9E View details
Amber LED: 4 flashes, then 2-second pause (not 4 red) Thermostat Wiring Warning

The control received a thermostat Y signal without a G signal. York states heating and cooling still operate normally; the indication flags a wiring issue and is unrelated to the four-red limit fault.

TM9E View details
Green LED slow flash: 2 seconds on, 2 seconds off Normal Standby

The furnace control is operating normally with no thermostat calls. This is the standby state, not a fault code.

TM9E View details
Amber LED slow flash: 2 seconds on, 2 seconds off Normal Heat Call

The control is operating normally with a heat call present. This slow amber flash is a status, not a one-flash fault, and does not by itself confirm the burner is lit.

TM9E View details
LED off (no color showing) No LED Indication

No LED is displayed. York lists lost control power, a blown fuse or a control failure as possible reasons, so a dark LED alone does not identify a failed board.

TM9E View details
LED steady on in red, green or amber, no flashing Control Failure

An LED lit steadily in red, green or amber indicates a control failure. York states the control is not field repairable.

TM9E View details