AMANA DIAGNOSTIC REFERENCE 19 VERIFIED CODES

Amana furnace error codes

Use this table for the two-character display on Amana AMVC96 and ACVC96 furnaces. Match the code exactly; its detail page explains the fault and what you can check before calling for service.

Jump to the code table · All furnace codes

Before you touch anything: the six signs that mean stop troubleshooting and call a pro →

Reading the Amana display

These furnaces show letters and numbers rather than counted flashes: E codes cover ignition, pressure, limit, and wiring faults, b codes cover the blower motor, and d codes cover memory card data. ON is a normal display. Write the code down exactly, since similar-looking codes can point to very different problems.

What this Amana page covers

This page covers only the AMVC96 and ACVC96 two-stage variable-speed display codes. These models share a control platform with Goodman, and the definitions come from Goodman-platform source documents for that shared control. Goodman single-LED flash codes and GMEC96 or GMVM97 codes are not covered here and should not be applied to these models.

Amana display code quick reference

Amana furnace codes and supported model families
Code or flash pattern Meaning Model family Details
E0display E0 Ignition Lockout (E0)

Three failed ignition cycles — the control can't establish measurable combustion and locks out. Same reset as flash models: thermostat OFF 5–20 s, or kill power ≥5 s.

AMVC96 · ACVC96 View details
E1display E1 Low-Stage Pressure Switch Stuck Closed (E1)

The low-stage pressure switch reads closed while the inducer is off. The control waits until the fault clears. Cause per manual: faulty switch or shorted wiring.

AMVC96 · ACVC96 View details
E2display E2 Low-Stage Pressure Switch Stuck Open (E2)

The low-stage pressure switch doesn't close within 5 minutes of the inducer starting → 1-hour lockout, then auto-retry. Official causes: disconnected hose, faulty switch or wiring, blocked venting.

AMVC96 · ACVC96 View details
E3display E3 Open Primary, Auxiliary, or Rollout Limit (E3)

One of three protective limits opened: primary (overheat), auxiliary, or flame rollout. Blowers run until it closes. Official causes: dirty filter or duct restriction, faulty limit, blower issue, blocked flue.

AMVC96 · ACVC96 View details
E4display E4 Flame Sensed With No Call for Heat (E4)

Flame detected while the gas valve is de-energized. Blowers run continuously as protection. Same emergency profile as 5 flashes on flash-code models.

AMVC96 · ACVC96 View details
E5display E5 Open Fuse (E5)

The control detects its onboard fuse open and inhibits all operation except displaying the code. Official probable cause: a short in the low-voltage wiring.

AMVC96 · ACVC96 View details
E6display E6 Low Flame Sense Signal (E6)

Furnace runs, but the flame-sensor microamp signal fell below spec. Official: coated/oxidized sensor, wrong sensor position, or lazy flame from improper gas pressure.

AMVC96 · ACVC96 View details
E7display E7 Igniter Fault or No Ground (E7)

Official: check for a broken or improperly connected igniter; check for proper ground and correct.

AMVC96 · ACVC96 View details
E8display E8 High-Stage Pressure Switch Stuck Closed (E8)

The high-stage pressure switch is stuck closed when high stage is commanded — the furnace runs on LOW stage only regardless of thermostat demand.

AMVC96 · ACVC96 View details
E9display E9 High-Stage Pressure Switch Stuck Open (E9)

High-stage switch won't close. Official checklist: blocked or pinched switch hose, blocked flue and/or intake pipe, blocked drain, weak induced-draft blower, or a failing switch.

AMVC96 · ACVC96 View details
EAdisplay EA Reversed Line Polarity (EA)

115V or 24V power leads are reversed — the furnace refuses to run. Same fix family as the continuous-flash code on flash models.

AMVC96 · ACVC96 View details
d0display d0 No Shared Data (d0)

The control has no shared data set (it drives the variable-speed motor and airflow math). The furnace cannot function until a model-specific memory card loads the data. Display shows ON when accepted.

AMVC96 · ACVC96 View details
d4display d4 Invalid Memory Card Data (d4)

The control rejected the shared data set — memory cards are model-specific and a card for a different model will be refused.

AMVC96 · ACVC96 View details
b0display b0 ECM Blower Motor Not Running (b0)

The control can't detect the ECM blower running when it should be. Official causes: loose/disconnected wiring between motor and control, an open inductor (¾ HP and 1 HP motors), or a failed ECM motor.

AMVC96 · ACVC96 View details
b1display b1 ECM Motor Communications Lost (b1)

The furnace control can't talk to the ECM blower — the furnace won't operate. Causes: loose harness, failed motor, or failed control.

AMVC96 · ACVC96 View details
b2display b2 Motor Horsepower Mismatch (b2)

The connected motor's horsepower doesn't match the shared data set — the furnace refuses to run. Fix: correct motor, or correct data via the proper memory card.

AMVC96 · ACVC96 View details
b3display b3 ECM Motor in a Limiting Condition (b3)

The ECM hit a power, speed, or temperature limit and reduced output — the furnace keeps running at reduced airflow. Officially caused by blocked/clogged filters, restrictive or undersized ductwork, blocked inlet, or high ambient heat.

AMVC96 · ACVC96 View details
b4display b4 Motor Trips (b4)

The ECM motor sensed a loss of control or became overloaded and shut down.

AMVC96 · ACVC96 View details
ONdisplay ON Display Reads ON — Normal

Normal state. It also confirms the control accepted memory-card data after a board or card procedure.

AMVC96 · ACVC96 View details

Same control platform, other brand names: Goodman furnace codes

Not sure how to read the light?

Use the interactive blink decoder — tap the pattern you see and we'll match it.