HVAC●FAULTS
LENNOX DIAGNOSTIC REFERENCE 15 VERIFIED CODES

Lennox furnace error codes

This page covers the Lennox ML193UHE gas furnace when it has ignition control 103217-03. The board reports status with a red LED. Counted flash groups separated by a 3-second pause mean a fault. A slow 1-second on, 1-second off pattern or a continuous rapid flash is a normal state. Check both the full model number on the rating plate and the diagnostic label on the door before using this chart. A flash count tells you what the control observed. It does not by itself confirm which part has failed.

Jump to the code table · All furnace codes

Before you touch anything: the six signs that mean stop troubleshooting and call a pro →

How to read the red LED

Count the red flashes in one group, then wait for the 3-second pause before the group repeats. Each flash lasts about half a second. A slow, even blink (1 second on, 1 second off) means the furnace is idle, running the fan, or cooling. Continuous rapid flashing with no pause means a heat call is underway. It does not prove the burner is producing heat. A dark LED means no control power or a board fault. Note what you see without defeating the door switch.

What this chart covers

The chart lists all 15 live rows for control 103217-03: twelve numbered faults (1 to 5 and 7 to 13), the dark-LED fault state and two normal states. Code 6 is unused on this board. The same Lennox manual has a separate table for control 107163-01, including a solid-on state, and that table is not merged here. Documented models are ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C and ML193UH110XE60C. Code recall and clearing are service functions, not homeowner steps.

ML193UHE control 103217-03 red LED code chart

Lennox furnace codes and supported model families
Code or flash pattern Meaning Model family Details
Red LED: 1 flash, then 3-second pause Reversed Polarity

The ignition control has detected that the line-voltage supply is wired with reversed polarity. The control uses this code to report a power-wiring condition, not a failed component.

ML193UHE View details
Red LED: 2 flashes, then 3-second pause Improper Earth Ground

The ignition control has detected an improper earth ground at the furnace. The code reports the electrical condition the board sees; it does not identify where in the circuit the ground is missing.

ML193UHE View details
Red LED: 3 flashes, then 3-second pause Ignition or Flame Failure

During a heat demand, the burners either failed to ignite or the control lost the flame signal after ignition. The same three-flash code covers both events, so it does not tell you which one occurred.

ML193UHE View details
Red LED: 4 flashes, then 3-second pause Low Flame Signal

The control is reading a weak flame signal. Lennox's table pairs this code with a flame-sensor check and does not list it as a lockout.

ML193UHE View details
Red LED: 5 flashes, then 3-second pause Ignition Watchguard

The control reached its maximum number of ignition retries or recycles and entered Watchguard. Lennox service literature describes five total ignition trials followed by a 60-minute Watchguard period before the control tries again.

ML193UHE View details
Red LED: 7 flashes, then 3-second pause Limit Switch Open

The primary or secondary limit switch has opened. When the primary limit opens, the gas valve shuts and the blower runs; the same code also marks Watchguard if a limit stays open longer than 3 minutes.

ML193UHE View details
Red LED: 8 flashes, then 3-second pause Rollout Switch Open

The flame-rollout safety switch is open. The control closes the gas valve, and the switch requires a manual reset after a technician identifies and corrects the cause.

ML193UHE View details
Red LED: 9 flashes, then 3-second pause Pressure Switch Not Proven

During a heat demand, the pressure switch either did not close or opened after closing. It is part of the pressure-proving circuit tied to the combustion-air inducer and venting.

ML193UHE View details
Red LED: 10 flashes, then 3-second pause Pressure Switch Watchguard

The pressure switch opened five times during a single heat demand, so the control entered Watchguard. It reflects repeated loss of pressure proving rather than one isolated event.

ML193UHE View details
Red LED: 11 flashes, then 3-second pause Pressure Switch Closed

The pressure switch was already closed before the combustion-air inducer started. The control expects it open at that point, so the reading points to a switch or control-circuit condition.

ML193UHE View details
Red LED: 12 flashes, then 3-second pause Unexpected Flame

The control sensed flame while the gas valve was not energized. Flame should not be present then, so this is a safety condition, not a routine fault.

ML193UHE View details
Red LED: 13 flashes, then 3-second pause Low Line Voltage

The ignition control is reporting low line voltage on the furnace's power supply. The code identifies a supply condition, not a specific failed part in the furnace.

ML193UHE View details
Red LED off (dark, no flashing) No Power or Board Fault

A dark LED means the control has no power or has detected a board fault. It does not say which of the two applies.

ML193UHE View details
Red LED slow flash: 1 second on, 1 second off Normal Idle Status

This is a normal status. The control is idle with no heat demand, running the fan continuously, or operating in cooling mode.

ML193UHE View details
Red LED continuous rapid flash, no pause Heat Call in Progress

The control is reporting an active heat call and burner operation sequence. Lennox's 103217-03 table does not give exact on/off timing for this flash.

ML193UHE View details

Not sure how to read the light?

Use the interactive blink decoder — tap the pattern you see and we'll match it.

Which furnace codes do Americans search most? 2026 search-demand snapshot →